Consider adding short-to-ground fault option to the bus model

Aperta
#605 1 commento 1 reazione 1 assegnatario Vedi su GitHub

I maintainer di solito rispondono entro 1 giorno

@lukelowry ci sta già lavorando.

Dal 5/10/2026.

Valutazione

Questa issue non è ancora stata valutata.

Descrizione

new model
Summary

Add option to the PhasorDynamics::Bus to create short-to-ground fault, as opposed to using a separate BusFault object attached to the bus.

Rationale

With current implementation one needs to modify the case file whenever one needs to add a fault. This becomes impractical, especially when carrying out a sweeping contingency for a large case.

Description

Implement fault within PhasorDynamics::Bus model itself in a similar fashion as it was done in BusFault component. This would add following parameters to the Bus model:

  • Fault on/off (bool)
  • Short-to-ground impedance (RealT)

Jacobian stamp for the "fault-able" bus would need to be augmented with additional derivatives, which would be set to zero when there is no fault.

Additional information

No response

Lingua principale
C++
Stelle
27
Fork
11
Merge medio
2g 21h
PR unite (30g)
15

Preparare l'ambiente

Apri in Codespaces

Avvia il container di sviluppo del progetto nel browser, con il tuo account GitHub.

Come iniziare

  1. Leggi tutta la issue e poi la guida ai contributi del progetto.
  2. Commenta sulla issue per dire che te ne occupi tu — evita che due persone facciano lo stesso lavoro.
  3. Fai un fork del repository e lavora su un branch.
  4. Apri una pull request che faccia riferimento al numero della issue.

Altre issue di ORNL/GridKit

Tutte le issue di ORNL/GridKit

Issue simili

Altre issue su C++

Ricevi le nuove issue nella tua casella

Un breve riepilogo di issue GitHub adatte ai principianti.