September design requirements: complete RCICS door assembly

オープン
#4 コメント 4 件 リアクション 0 件 担当者 4 名 GitHub で見る

@Yhya99 がすでに取り組んでいます。

2026年9月18日 から。

評価

この issue はまだ評価されていません。

説明

documentation

Purpose

Define and complete the September RCICS door-assembly design based on the 10 and 17 September 2026 core-team reviews and the current RCICS Requirements Document and Project Plan.

The September iteration should treat RCICS as a complete replacement door leaf/assembly for contact-and-droplet isolation, not only as a viewing-window retrofit. The design must remain locally fabricable in quantities of tens using commonly available materials and tools.

Confirmed design direction

  • Use a rigid transparent viewing panel (Plexiglas/acrylic) in a fully framed portal.
  • The portal/window should be installed into the door opening as a framed assembly.
  • Develop a complete door option so exposed cut-door cross-sections are covered and sealed.
  • Prefer steel where it is more readily available; PVC or another non-porous door material may be proposed as an alternative.
  • Do not require specialized fabrication equipment for field installation.
  • Preserve safe latch/handle operation, emergency egress, and sufficient opening for a patient bed/gurney.
  • This is for contact/droplet isolation only, not airborne/negative-pressure isolation.

Required Engineering Work

1. Mechanical Engineer (Design and Fabrication)

  • Create the dimensioned full-door assembly drawing/CAD model.
  • Provide at least three sealable ports for tubing, IV lines, and cables.
  • Show the door, Plexiglas panel, Z-section sandwich frame, ports, transfer opening, hinges, latch, bottom seal, and critical clearances.
  • Add a panel cross-section and exploded assembly view.
  • Mark assumed and field-adjustable dimensions.
  • Finalize how the Plexiglas is captured without over-compression or cracking.
  • Compare welded versus bolted/riveted frame construction and select one.
  • Specify fasteners, backing plates, spacing, edge distances, tightening guidance, and acrylic expansion clearance.
  • Define gasket and sealant locations.
  • Seal exposed door-core/cut edges and avoid liquid traps.
  • Detail attachment to hollow-metal, solid-core, and fabricated PVC/metal doors.
  • Add strain relief, removable closures, and retention features to all ports.
  • Confirm total weight, hinge capacity, and two-person installation suitability.

2. Biomedical Engineer (Clinical Use and Safety)

  • Confirm expected equipment, tubing, cables, and connector sizes with WHO-Techne.
  • Define the larger transfer-opening requirements.
  • Confirm port placement, strain relief, and clear viewing area.
  • Verify cleanability and compatibility with hospital disinfectants.
  • Review panel security, latch operation, emergency egress, clear opening, and bottom seal.
  • Define clinical and facility acceptance criteria.

3. Procurement (Materials and Cost)

  • Confirm regional availability of Z/L profiles, acrylic, gaskets, silicone bungs, sealants, fasteners, and backing plates.
  • Source 1-inch PVC tubes/caps and 4-inch PVC cap fittings.
  • Select non-porous, corrosion-resistant, and disinfectant-compatible materials with engineering approval.
  • Update the September BOM while retaining the original/August BOM.
  • Include quantities, specifications, suppliers, substitutes, lead times, and prices.
  • Estimate material costs and list labor assumptions separately.

4. Technical Writer (Installation Documentation)

  • Prepare concise, illustrated instructions covering:
    • Field measurement and door cutout
    • Cut-edge sealing
    • Frame and panel assembly
    • Gasket and sealant application
    • Port and strain-relief installation
    • Door hanging and hardware checks
    • Final cleaning
  • Maintain consistent part names across drawings, BOM, and instructions.
  • Add revision information and clearly document assumptions.
  • Create a facility acceptance checklist covering fit, seals, panel security, ports, hardware, egress, and cleanability.

5. Research (Evidence and Field Input)

  • Research acrylic mounting, expansion clearance, fastener spacing, and gasket compression.
  • Compare welded and mechanically joined frame options for local fabrication.
  • Check material and sealant compatibility with common hospital disinfectants.
  • Gather field input on materials, fabrication tools, door types, and clinical equipment.
  • Identify applicable door, glazing, infection-control, and emergency-egress guidance.

Priority Order

  1. Finalize the Z-frame cross-section.
  2. Confirm port and equipment requirements.
  3. Confirm materials and update the BOM.
  4. Complete the engineering drawings.
  5. Prepare the installation instructions.
  6. Build and validate the prototype.
主要言語
言語のデータがありません
スター
2
フォーク
0
平均マージ
1分
マージ済み PR(30日)
2

環境構築

このプロジェクトの環境構築ファイルはまだ確認していません。まず README を読み、一般的な手順ははじめてのコントリビューションガイドを参照してください。

はじめの一歩

  1. issue を最後まで読み、次にプロジェクトのコントリビューションガイドを読みます。
  2. 着手することを issue にコメントします — 二人が同じ作業をするのを防げます。
  3. リポジトリをフォークし、ブランチを切って変更します。
  4. issue 番号を参照したプルリクエストを送ります。

新しい issue をメールで受け取る

初心者向けの GitHub issue を短くまとめたダイジェスト。